<p>end using various techniques to ensure synchronization with minimal data traffic. The master may poll its subordinate unit (Master to RTU or RTU to IED) for changes of data on a periodic basis. Analog value changes will usually be reported only on changes outside a set limit from the last transmitted value. Digital (status) values observe a similar technique and only transmit groups (bytes) when one included point (bit) changes.  Another method used is where a subordinate unit initiates an update of data upon a predetermined change in analog</p><p>